12-6* Ethernet POWERLINK
6.13.8
12-60 Node ID
Default value:
1
Setup:
2 setups
Data type:
Uint8
Enter the node ID in this parameter or alternatively in the hardware switch. To adjust the node ID in this parameter, set the hardware
switch to 0 or to 255 (all switches set to [ON] or to [OFF]). Otherwise, this parameter shows the actual setting of the switch. The settings
of this parameter take effect at the next power-up cycle.
12-62 SDO Timeout
Default value:
15000 ms
Setup:
All setups
Data type:
Uint32
This parameter is the SDO Timeout in ms. The value of this parameter is read during communication initialization into Object 1300h.
410
| © 2024.09
Description
PDI operational
PDI watchdog status
Enhanced link detection
–
Physical link on port 0
Physical link on port 1
Reserved
Reserved
Loop port 0
Communication on port 0
Loop port 1
Communication on port 1
Reserved
Reserved
Reserved
Reserved
Bit = [0]
EEPROM not loaded, PDI not
operational
Watchdog expired
Deactivated for all ports
–
No link
No link
–
–
Open
No stable communication
Open
No stable communication
–
–
–
–
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter Descriptions
Bit = [1]
EEPROM loaded correctly, PDI
operational
Watchdog reloaded
Activated for all ports
Reserved
Link detected
Link detected
–
–
Closed
Communication established
Closed
Communication established
–
–
–
–
Range, 1 - 239
0
True
Range, 0 - 2000000000 ms
-3
True
AU275636650261en-003201 / 130R0334