9-18 Node Address
Default value:
126
Setup:
1 setup
Data type:
Uint8
Enter the station address in this parameter or, alternatively, in the hardware switch. To adjust the station address in this parameter, set
the hardware switch to 126 or 127 (that is all switches set to ON). Otherwise, this parameter shows the actual setting of the switch.
9-22 Telegram Selection
Default value:
[100] None
Setup:
1 setup
Data type:
Uint8
Select a standard PROFIBUS telegram configuration for the drive as an alternative to the freely configurable telegrams in parameter 9-15
PCD Write Configuration and parameter 9-16 PCD Read Configuration.
Option
Name
[1]
Standard telegram 1
[100]*
None
[101]
PPO 1
[102]
PPO 2
[103]
PPO 3
[104]
PPO 4
[105]
PPO 5
[106]
PPO 6
[107]
PPO 7
© 2024.09
Description
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Description
AU275636650261en-003201 / 130R0334 |
Parameter Descriptions
Range, 1 - size related
0
True
Option
–
True