Programming Guide | VLT® AutomationDrive FC 301/FC 302
Option
Name
[0]
Disabled
[1]
Enabled
[2]
Password
[3]
Hand Off/On
[4]
Hand Off/On w. Passw.
[9]
Enabled, ref=0
0-41 [Off] Key on LCP
Default value:
–
Setup:
All setups
Data type:
Uint8
Option
Name
[0]
Disabled
[1]
Enabled
[2]
Password
0-43 [Reset] Key on LCP
Default value:
–
Setup:
All setups
Data type:
Uint8
Option
Name
[0]
Disabled
[1]
Enabled
[2]
Password
68
| © 2024.09
Description
No effect when [Hand On] is pressed. Select [0] Disabled to avoid
accidental start of the drive in hand-on mode.
The LCP switches to hand-on mode directly when [Hand On] is
pressed.
After pressing [Hand On] a password is required. If parameter
0-40 [Hand on] Key on LCP is included in My Personal Menu,
define the password in parameter 0-65 Personal Menu Password.
Otherwise define the password in parameter 0-60 Main Menu
Password.
When [Hand On] is pressed once, the LCP switches to Off mode.
When pressed again, the LCP switches to hand-on mode.
Same as option [3] Hand Off/On but a password is required (see
option [2] Password).
When switching to [Hand On], the reference is set to 0.
Parameter type:
Conversion index:
Change during operation:
Description
Avoids accidental stop of the drive.
Avoids unauthorized stop. If parameter 0-41 [Off] Key on LCP
is included in the Quick Menu, then define the password in
parameter 0-65 Personal Menu Password.
Parameter type:
Conversion index:
Change during operation:
Description
No effect when [Reset] is pressed. Avoids accidental alarm reset.
Avoids unauthorized start in auto-on mode. If parameter 0-43
[Reset] Key on LCP is included in the Quick Menu, define the
password in parameter 0-65 Personal Menu Password.
Parameter Descriptions
Option
–
True
Option
–
True
AU275636650261en-003201 / 130R0334