Programming Guide | VLT® AutomationDrive FC 301/FC 302
Option
Name
[229]
Vir. master on ref.
[231]
In power lim. mot.
[232]
In power lim. gen.
[233]
In power limit
[234]
PE power off
[246]
Emcy mode was act.
[247]
Emergency mode
[249]
Emcy m. OPR unexptected
[250]
Emcy mode limits
[254]
Testing emcy mode
5-41 On Delay, Relay
Default value:
0.01 s
Setup:
All setups
Data type:
Uint16
Enter the delay of the relay cut-in time. Select 1 of 2 internal mechanical relays in an array function. See parameter 5-40 Function Relay
for details.
262
| © 2024.09
Description
NOTICE
This option is available only with software version 48.XX.
The virtual master is running on the set reference.
NOTICE
This option is only available in FC 302.
NOTICE
This option is only available in FC 302.
NOTICE
This option is only available in FC 302.
The drive has been operating in emergency mode.
The drive is operating in emergency mode. See parameter group
24-0* Emergency Mode.
Emergency mode is not operating as expected, for example, live
zero monitoring on an analog input is activated.
During emergency mode operation, 1 of the critical alarms has
been activated and suppressed by emergency mode. This may
lead to reduced drive performance and expected lifetime before
service is required.
Emergency mode was activated in a special test mode where the
drive stops on all alarms.
Parameter type:
Conversion index:
Change during operation:
Parameter Descriptions
Range, 0.01 - 600 s, Array [9]
-2
True
AU275636650261en-003201 / 130R0334