Programming Guide | VLT® AutomationDrive FC 301/FC 302
This parameter cannot be adjusted while the motor is running.
Use this parameter to configure the drive for either high or normal overload. When selecting the drive size, always review the technical
data in the operating guide or the design guide to know the available output current.
Option
Name
[0]
High torque
[1]
Normal torque
1-05 Local Mode Configuration
Default value:
[2] As mode par. 1-00
Setup:
All setups
Data type:
Uint8
Select which application configuration mode (parameter 1-00 Configuration Mode), that is application control principle, to use when a
local (LCP) reference is active. A local reference can be active only when parameter 3-13 Reference Site is set to [0] Linked to Hand/Auto
or [2] Local. By default the local reference is active in hand-on mode only.
Option
Name
[0]
Speed open loop
[1]
Speed closed loop
[2]*
As mode par. 1-00
[4]
Positioning
1-06 Clockwise Direction
Default value:
[0] Normal
Setup:
All setups
Data type:
Uint8
This parameter cannot be adjusted while the motor is running.
This parameter defines the term clockwise corresponding to the LCP direction arrow. Used for easy change of direction of shaft rotation
without swapping motor wires.
82
| © 2024.09
NOTICE
Description
Allows up to 160% overtorque.
For oversized motor. Allows up to 110% overtorque.
Parameter type:
Conversion index:
Change during operation:
Description
Parameter type:
Conversion index:
Change during operation:
NOTICE
Parameter Descriptions
Option
–
True
Option
–
False
AU275636650261en-003201 / 130R0334