Switch-On / Shutdown (On / Off) Terminal 37 - Control Word 1, Bit 0 - Siemens 6RA7086-6KS22 Operating Instructions Manual

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

Function descriptions
Sequence of operations for cancellation of "Fast stop":
1.
Stop applying "Fast stop" command
2.
Enter "Standstill" command (e.g. via "Switch-on/shutdown" terminal)
3.
Converter exits operating state o8
Switch-on/Shutdown
Fast stop
Internal fast stop
Internal controller enable
Internal setpoint enable
n < n
(P370,P371)
min
Actual speed
Brake control signal (B0255)
(holding brake)
Internal standstill
field input
The "Fast stop" command need only be applied as a short pulse (> 10 ms). It is then stored
internally. The memory can be reset only by applying the "Shutdown" command.
All "Fast stop" commands are ANDed by the SIMOREG converter, i.e. all commands must be set
to "No fast stop" before the function can be deactivated.
When n < n
prevents the drive from attempting to brake again if the motor is turned by external forces.
The n < n
9.3.3

Switch-on / shutdown (ON / OFF) terminal 37 - control word 1, bit 0

The "Switch-on / shutdown" (ON / OFF) function is controlled via the "Switch-on command of ON /
OFF1" (= ANDing between signal from terminal 37 and binector selected in parameter P654, level- or
edge-triggered, see below) and bit 0 of connector selected as the control word in P648.
The following operating modes are possible:
P648 = 9:
P648 ≠ 9:
P445 = 0:
9-8
P087
P087 Brake release time (positive in this example)
P088 Brake closing time
P258 Delay for automatic field current reduction
(P370, P371) is reached for the first time, an internal interlock is activated which
min
signal then disappears again.
min
The control bits in control word 1 are input bit-serially. "ON / OFF" is controlled via the
"Switch-on command of ON / OFF1".
The connector selected in P648 is used as control word 1. Bit 0 of the control word is
ANDed with the "Switch-on command of ON / OFF1" to produce the "ON / OFF"
command (ON only if both signals are log. "1").
The "Switch-on command of ON / OFF1" is generated as an AND operation between the
signal from terminal 37 and the binector selected in P654 (level-triggered, 0 = shutdown,
1 = switch-on).
ON
External fast stop
No fast stop
No fast stop
Internal fast stop
Controller enabled
Setpoint enabled
n > n
min
Setpoint reached
Release brake
No standstill field
Shutdown
Controller disabled
Setpoint =0
n < n
min
Setpoint reached
Close brake
Sandstill field
P088
P258
SIEMENS AG
SIMOREG DC Master
Operating Instructions
05.05