10.10 Switch on, switch off, enable

Wiring example for a USS bus
1)
The shields for the interface cables must be connected directly on the devices (using a clamp, for example) to
device or cabinet ground, with a low level of impedance.
2)
Twisted cable, e.g. LIYCY 2×0.5 mm
that the difference in ground potentials between the link partners remains below 7 V.
Figure 10-57 USS bus
10.10
Switch on, switch off, enable
10.10.1
Switch on/Switch off (ON/OFF1) – Control word bit 0
The "Switch on/Shutdown" (ON/OFF1) function is controlled using the "ON/OFF1 switch-on
command" (= ANDing the signal from terminal X177.12 with the signal selected using
p0840).
The following operating modes are possible here:
p50445 = 0:
p50445 = 1:
552
; with longer cables, an equipotential bonding cable should be used to ensure
2
The "ON/OFF1 switch-on command" takes the form of ANDing the signal
from terminal X177.12 with the signal selected using p0840 (level-controlled,
0 = shutdown, 1 = switch on).
Edge triggering of "ON/OFF1 switch-on command":
The switch-on command is saved when a 0 → 1 transition takes place
(see function diagram 3130 in the SINAMICS DCM List Manual). The binector
selected using p50444 must be in the log. "1" state at this point. The memory
is reset when this binector enters the log. "0" state.
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A