Co: Torque Actual Value / Actual Torque; Co: Active Power Actual Value / P_Act; Co: Flux Setpoint / Flex Setp; Co: Flux Actual Value / Actual Flux - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Parameters
7.2 Parameter list
r0080[0...1]

CO: Torque actual value / Actual torque

Access level: 3
Can be changed: -
Unit group: 7_1
Min:
- [Nm]
Description:
Display and connector output for actual torque value.
Index:
[0] = Unsmoothed
[1] = Smoothed with p0045
Dependency:
See also: r0031, p0045
Note
The value is available smoothed (r0031 with 100 ms, r0080[1] with p0045) and unsmoothed (r0080[0]).
r0082[0...2]

CO: Active power actual value / P_act

Access level: 3
Can be changed: -
Unit group: 14_5
Min:
- [kW]
Description:
Displays the instantaneous active power.
Index:
[0] = Unsmoothed
[1] = Smoothed with p0045
[2] = Electric power
Dependency:
See also: r0032
Note
The mechanical active power is available smoothed (r0032 with 100 ms, r0082[1] with p0045) and unsmoothed
(r0082[0]).
r0083

CO: Flux setpoint / Flex setp

Access level: 4
Can be changed: -
Unit group: -
Min:
- [%]
Description:
Displays the flux setpoint.
r0084[0...1]

CO: Flux actual value / Actual flux

Access level: 4
Can be changed: -
Unit group: -
Min:
- [%]
Description:
Displays the flux actual value.
Index:
[0] = Unsmoothed
[1] = Smoothed
496
Calculated: -
Scaling: p2003
Unit selection: p0505
Max:
- [Nm]
Calculated: -
Scaling: r2004
Unit selection: p0505
Max:
- [kW]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
- [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
- [%]
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6714, 6799
Factory setting:
- [Nm]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6714, 6799
Factory setting:
- [kW]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 5722
Factory setting:
- [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6730, 6731
Factory setting:
- [%]
SINAMICS G120X converter