Application
Use this procedure to verify the correct resistance of the wrist strap grounding
cord. This resistance must be low enough for static electricity to discharge
from a person. This resistance must be high enough to prevent electrocution
if the equipment develops a short-circuit while the person wears a wrist strap.
Interval
Perform this procedure every month.
Common procedures
There are no common procedures.
Action
This procedure contains a summary flowchart and a list of steps. Use the
flowchart to review the procedure. Follow the steps to perform the procedure.
OPM routine maintenance procedures 13-85
Testing wrist strap grounding cords
DMS-100 Family OPM Maintenance Manual XPM14 and up
OPM