power control unit (PCU)
battery control unit (BCU)
rectifiers
batteries
FSP
OPM grounding network
The cabinet requires a standard 30A, single-phase, 208V commercial ac
supply. The battery reserve of the OPM consists of: eight strings of Yuasa
A037761 or six strings of Eagle-Picher A0386201 batteries. The OPM-256
has 6 strings. When the batteries are installed and at 100% capacity, this
reserve corresponds to 178 Ah Yuasa and 162 Ah Eagle-Picher. Batteries
calculated at 80% capacity, which corresponds to 142 Ah Yuasa and 129.6 Ah
Eagle-Picher reserve power, are at the end-of-life.
When the external temperature is -40°C (104oF), the battery reserve for the
OPM-640 and OPM-256 is at 80% capacity. At 80% capacity the batteries
provide 8 h of backup power at a call rate of 300 call seconds (CCS). During
extended power outages, an emergency generator connected to the emergency
power generator port can supply ac power.
Cable-connecting compartment
The cable-connecting compartment is in the end-access compartment. This
compartment provides outside plant cable protection and termination and
cross-connection with the following:
entrance for buried incoming ac power and ground cable
entrance for ground rod or cable from ground rod
entrance for buried incoming subscriber pairs
entrance for buried pairs of incoming DS-1 lines
entrance for buried pairs incoming special service lines
the cabinet ground bar
one gas or solid state protector for each subscriber pair
12 gas tube or solid state protectors for DS-1 lines
88 gas tube or solid state protectors for special service lines
BIX terminals to connect subscriber pairs, DS-1 lines and special service
lines
DMS-100 Family OPM Maintenance Manual ISN07 (TDM)/SN07 (DMS) and up
OPM maintenance summary 1-15