Replacing an NT3X09 card in an RMM
At your current location
1
Obtain a replacement card. Ensure that the replacement card has the same
product equipment code (PEC), including suffix, as the card to be removed.
At the MAP terminal
2
Determine the suffix of the NT3X09 card to be replaced.
If suffix is
BA
AA
3
Access the TTP level of the MAP terminal and post the RMM that contains
the card to be replaced by typing
>MAPCI;MTC;TRKS;TTP;POST P RMM rmm_no ckt_no
and pressing the Enter key.
where
rmm_no
is the number of the RMM shelf in which the card is to be replaced
ckt_no
is the number of the first circuit where the NT3X09 card is physically
located
Example of a MAP response:
LAST CIRCUIT = 27
POST CKT IDLED
SHORT CLLI IS:
OK, CLLI POSTED
POST
20
TTP 6–006
CKT TYPE
OG
MISC RMM 0 0
4
Check the status of the RMM.
If RMM status is
MB, PMB, RMB
other
OPM card replacement procedures
in an OPM RMM
1118
DELQ
BUSY Q
PM NO.
COM LANG
MTADRIVER 20
DMS-100 Family OPM Maintenance Manual XPM14 and up
Do
step 3
step 9
DIG
STA S R DOT TE R
LO
Do
step 6
step 5
8-85
NT3X09
(continued)