7-70 OPM alarm clearing procedures
Ext FSP
OPM cabinet major
At the MAP terminal
106
107
108
At the OPE frame
109
110
111
112
113
297-8361-550 Standard 04.01 September 2000
(end)
To access the EXT level of the MAP display, type
>MAPCI;MTC;EXT
and press the Enter key.
Determine if an FSP alarm is present.
If an FSP alarm
is present, and you did not access all the frames with
an FSP alarm
is present, and you did access all the frames with an
FSP alarm
is not present
Perform the correct procedure for the type of frame that has the FSP alarm.
When you complete the procedure, return to this step.
Make a visual inspection of the FSP. Check circuit breakers CB8 and CB9.
If circuit breakers
are tripped
are not tripped
Reset the circuit breaker (CB8 or CB9). Move the switch to the ON/OFF
position, and immediately back to the ON position. (The LED light goes OFF).
If circuit breaker
trips again
remains ON (LED goes off)
Check the table of contents for the LCM talk battery alarm procedure.
Perform the procedure. When you complete the procedure, return to this
step.
For additional help, contact the next level of support.
The procedure is complete.
Do
step 108
step 112
step 113
Do
step 110
step 113
Do
step 111
step 113