Nortel DMS-100 Series Maintenance Manual page 356

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

8-16 OPM card replacement procedures
NT0X91AE
in an OPM
(continued)
8
9
10
11
12
13
At the OPM cabinet
14
15
16
17
297-8361-550 Standard 04.01 September 2000
rame_no
is the number of the frame where the LCM is located
lcm_no
is the number of the LCM unit associated with the faulty card
Busy LCM unit 0 by typing
>BSY
UNIT 0
and pressing the Enter key.
Post the RMM that is controlled by the alarm and control card as recorded in
step 5 by typing
>POST RMM rmm_no
and pressing the Enter key.
where
rmm_no
is the number of the RMM to be posted, as recorded in step 5
Busy the RMM by typing
>BSY
and pressing the Enter key.
Post the ESA processor that is controlled by the alarm and control card as
recorded in step 5 by typing
>POST ESA esa_no
and pressing the Enter key.
where
esa_no
is the number of the ESA processor to be posted, as recorded in step 5
Busy the ESA processor by typing
>BSY
and pressing the Enter key.
Set CB1 as recorded in step 4 to ON.
Put on a wrist strap.
Set CB1 as recorded in step 4 to OFF.
Set CB5 as recorded in step 4 to OFF.
Unscrew the slotted nut located on the left-hand side of the FSP.