7-120 OPM alarm clearing procedures
PM PES
critical, major, minor
18
19
20
21
22
23
297-8361-550 Standard 04.01 September 2000
(end)
and press the Enter key.
If the system
does not display W under BCC
displays W under BCC
This system generates the alarm if only one or more equipped battery string
pair is on the load bus. Consult office records or operating company
personnel to determine why more than one battery string pair does not
connect to the load bus.
If battery return to load bus
is installed
is not installed
To place the battery on the load bus, type
>LOADB n
and press the Enter key.
where
n
is the battery string pair number 0, 1, 2, or 3
If the system response
is not OK
is OK
To enable the audit, type
>AUDIT ENABLE
and press the Enter key.
Go to step 23.
You cannot clear the condition from the office. Advise outside personnel and
contact your maintenance support group.
The procedure is complete. If the system displays additional alarms,
proceed to the correct alarm clearing procedure.