Nortel DMS-100 Series Maintenance Manual page 57

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

Table 6 Battery rotation and testing parameters entered in table OFCSTD
Parameter
OPM_VOLT_TST
_CHG
OPM_VOLT_TST
_LTU_
ADJUSTMENT
Table OPMINV
The user can set field ENABATST in table OPMINV to Y(yes) or N (no) for
each OPM. When set to Y, the system performs weekly battery testing. When
set to N, the system bypasses weekly battery testing.
Battery rotation and test cycle
The complete battery rotation and test cycle last 4 weeks and repeats. The
following table shows the rotation and test cycle. The present audit week
appears under the header Week at the PES MAP level.
legend for the following table is:
Default
Range
value
0 through
-509
-600
0 through 50
10
Note: Battery strings 3 and 7 contain datafill with an N when the system
equips Eagle-Picher A0386201 batteries. The system equips a maximum of
six battery strings for each OPM with the Eagle-Picher batteries.
O/C open circuit
DISCHG discharge through NT8X02 card
CHG charge bus
DMS-100 Family OPM Maintenance Manual ISN07 (TDM)/SN07 (DMS) and up
OPM maintenance summary 1-41
Description
Indicates this parameter is the comparison
value for the voltage of the battery string during
the post-charge test. The default value for
Yuasa NP24-12 and Eagle-Picher A0386201
batteries is -509 and corresponds to -50.9V. If
this parameter is set to zero, the post charge
test is not performed.
Indicates that the comparison voltages for the
open circuit, discharge and post-charge tests
are specified for the MTU. The MTU has 0.5%
accuracy and 0.1V resolution. This parameter
adjusts the comarison values when an LTU is
used to test batteries instead of an MTU. The
LTU has 2% accuracy and 1V resolution.
The