7-10 OPM alarm clearing procedures
LCM
critical
(continued)
20
21
22
297-8361-550 Standard 04.01 September 2000
PM Type: LCM
Int. No.: 20
Memory Size: 256K
ESA equipped: Yes, Intraswitching is On
Loadnames:LCMINV –XLCM06AW,Unit0:XLCM06AW, Unit1:XLCM06AW
Node Status: (OK, FALSE)
Unit 0 Status: (OK, FALSE)
Unit 1 Status: (OK, FALSE)
Site Flr RPos Bay_id
REM1
01 D04
LCM 40
If OPM
is equipped with ESA
is not equipped with ESA
To determine if the OPM is in ESA, perform a manual check for a dial tone at
the remote. A PM alarm appears on the MAP screen that indicates the OPM
is in ESA.
If the OPM
has dial tone
does not have dial tone
Determine if the OPM has the ESA timer set for manual recovery from ESA.
To access table OFCENG, type:
>TABLE OFCENG
and press the Enter key.
To check the OPM time of exit, type:
>POS RLCM_XPMESAEXIT
and press the Enter key.
Example of a MAP response:
PARMNAME
–––––––––––––––
RLCM_XPMESAEXIT
If PARMVAL
is set to zero
is greater than zero
Status index: 9
Shf
Description
04
LCM
40
Do
step 20
step 27
Do
step 21
step 27
PARMVAL
3
Do
step 23
Allow the system to recover the
OPM. Go to step 33.
Node_No: 165
Slot
EqPEC
0:0
6X04AA