8-70 OPM card replacement procedures
NT2X70
in an OPM HIE
At the HIE shelf
40
41
42
43
44
297-8361-550 Standard 04.01 September 2000
(continued)
Power down the NT2X70 card in slot 22 of the HIE shelf by setting the
ON/OFF switch on the power converter faceplate to the OFF position. Both
the converter FAIL LED and FRAME FAIL lamp on the frame supervisory
panel (FSP) will be ON. An audible alarm may sound. If an alarm does
sound, silence it by typing
>SIL
and pressing the Enter key.
If NT2X70 is in
shelf 5 slot 25
shelf 5 slot 22
Replace the NT2X70 card in slot 22 using the common replacing a card
procedure in this document. When you have completed the procedure, return
to this point
Power up the NT2X70 card in slot 22 of the HIE shelf as follows:
a
Ensure that the NT2X70 card is inserted. A major audible alarm may
sound. This alarm is silenced when power is restored to the converter.
b
Set the POWER switch to the ON position.
If NT2X70 suffix is
AE, or AF
AA, AB, AC, or AD
Toggle the ON/OFF/RESET switch on the power converter faceplate to the
RESET position and hold while setting the circuit breaker on the FSP to the
ON position. Both the converter FAIL LED and FRAME FAIL lamp on the FSP
will go OFF, release the ON/OFF/RESET switch. Go to step 45.
Press the RESET button on the power converter faceplate while setting the
circuit breaker on the FSP to the ON position. Both the converter FAIL LED
and FRAME FAIL lamp on the FSP will go OFF, release the RESET button.
WARNING
Static electricity damage
Wear a wrist strap connected to the wrist strap grounding
point of a frame supervisory panel (FSP) while handling
circuit cards. This protects the cards against damage caused
by static electricity.
Dotrip circuit breaker
CB1 on FSP
CB4 on FSP
Dotrip circuit breaker
step 43
step 44