Nortel DMS-100 Series Maintenance Manual page 331

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

FSP
condition of the frame supervisory
panel
.
FSP not faulty
F
FSP fault detected
BCC
condition of the battery charger controller
.
normal load bus configuration in use
W
one or more battery strings not
connected to the load bus
0123
states of the battery string pairs
.
string connected to load bus
CHG
string connected to charge bus
BSY
driver card manual busy or offline
O/C
string open-circuit
DIS
string connected to discharge test bus
F
string failed system testing
string not equipped
BCCFUSES
state of the battery charger controller fuses
.
fuses not faulty
F
faulty fuse
BCCDVR
state of the battery charger controller driver card
.
in service, no fault detected
M
manually busy
S
system busy
P
peripheral busy
PESALRM
state of the power and environmental system alarm scan card
.
in service, no fault detected
M
manually busy
S
system busy
P
peripheral busy
OPM alarm clearing procedures
critical, major, minor
DMS-100 Family OPM Maintenance Manual XPM14 and up
7-111
PM PES
(continued)