Nortel DMS-100 Series Maintenance Manual page 311

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

and press the Enter key.
where
lcm_unit
is the LCM unit to be busied (0 or 1)
27
To test the busied unit, type
>TST UNIT lcm_unit
and press the Enter key.
where
lcm_unit
is the LCM unit to test (0 or 1)
If test
passed
failed, and the system produces
a card list
failed, but the system does not
produce a card list
28
To attempt to return the LCM to service, type
>RTS UNIT lcm_unit
and press the Enter key.
where
lcm_unit
is the LCM unit to return to service (0 or 1)
If RTS
passed
failed
29
The card list identifies the cards with possible faults. Replace the cards one
at a time in the order listed.
If you
replaced the last card
did not replace the last card
30
For additional help, contact the next level of support.
31
Go to the Card Replacement Procedures to replace the first (or next) card on
the card list. For an OPM, notify outside operating company personnel that
OPM alarm clearing procedures
DMS-100 Family OPM Maintenance Manual XPM14 and up
minor
Do
step 28
step 29
step 30
Do
step 32
step 30
Do
step 31
step 30
7-91
LCM
(continued)