Nt2X09 In An Opm Rmm - Nortel DMS-100 Series Maintenance Manual

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

8-32 OPM card replacement procedures
NT2X09
in an OPM RMM
7
At the RMM shelf
8
9
10
11
12
297-8361-550 Standard 04.01 September 2000
(continued)
rmm_no
is the number of the RMM shelf in which the card is to be replaced
Example of a MAP display:
SysB
PM
0
RMM
0
RMM
0
InSv
Busy the RMM by typing
>BSY
and pressing the Enter key.
DANGER
Static electricity damage
Wear a wrist strap connected to the wrist strap grounding
point of a frame supervisory panel (FSP) while handling
circuit cards. This protects the cards against damage caused
by static electricity.
Power down the unit by setting the ON/OFF switch on the power converter
faceplate to the OFF position. Both the converter FAIL LED and FRAME FAIL
lamp on the frame supervisory panel (FSP) will be ON. An audible alarm may
sound. If an alarm does sound, silence it at the MAP terminal by typing
>sil
and pressing the Enter key.
Replace the NT2X09 card using the common replacing a card procedure in
this document. When you have completed the procedure, return to this point.
Power up the RMM unit as follows:
a
Ensure that the converter (NT2X09) is inserted. A major audible alarm
may sound. This alarm is silenced when power is restored to the
converter.
b
Set the POWER switch to the ON position.
Press the RESET button on the power converter while setting the circuit
breaker on the frame supervisory panel (FSP) to the ON position. Both the
converter FAIL LED and FRAME FAIL lamp on the FSP will be ON.
If you were directed to this procedure from another maintenance procedure,
return now to the procedure that directed you here and continue as directed;
otherwise, continue with step 13.
ManB
Offl
2
2
0
1
CBsy
ISTb
0
7
0
0
InSv
21
6