Replacing an NT2X48 card in an RMM
At the MAP display
1
Obtain a replacement card. Ensure that the replacement card has the same
product equipment code (PEC), including suffix, as the card to be removed.
2
Access the TTP level of the MAP and post the ESA digitone receivers
associated with the card to be replaced by typing
>MAPCI;MTC;TRKS;TTP;POST P RMM rmm_no ckt_no
and pressing the Enter key.
where
rmm_no
is the number of the RMM shelf in which the card is to be replaced
ckt_no
is the number of the first circuit where the NT2X48 card is physically
located.
Example of a MAP response:
LAST CIRCUIT = 27
POST CKT IDLED
SHORT CLLI IS:
OK, CLLI POSTED
POST
3
TTP 6–006
CKT TYPE
OG
RMM
3
Busy the trunks that are associated with the card to be replaced by typing
>BSY;NEXT
and pressing the Enter key.
Note: Repeat this step for each circuit associated with the NT2X48 being
replaced.
OPM card replacement procedures
1125
DELQ
BUSY Q
PM NO.
COM LANG
0 0
ESAGDTR 11
DMS-100 Family OPM Maintenance Manual XPM14 and up
in an OPM RMM
DIG
STA S R DOT TE R
INB
8-47
NT2X48
(continued)