7-44 OPM alarm clearing procedures
LCM
major
(continued)
16
17
297-8361-550 Standard 04.01 September 2000
and press the Enter key.
where
site
is the site name of the OPM (alphanumeric)
frame
is the frame number of the OPM (0 to 511)
lcm
is the number of the OPM
WARNING
If you do not allow the time required for the system to clear the
alarm, a false alarm indication can occur.
Allow 3 to 5 minutes for the system to clear the alarm before
you proceed to the next step.
To busy the OPM unit associated with the alarm, type
>BSY UNIT
lcm_unit
and press the Enter key.
where
lcm_unit
is the LCM unit to be busied (0 or 1)
To test the busied unit, type
>TST UNIT lcm_unit
and press the Enter key.
where
lcm_unit
is the LCM unit to test (0 or 1)
If test
fails because of a load error
passes
fails, and the system produces a
card list
fails, and the system did not pro-
duce a card list
Do
step 18
step 19
step 20
step 21