At the MAP display
4
Repost to verify the signal distribution circuits on the card that was replaced
by typing
>POST P RMM rmm_no ckt_no
and pressing the Enter key.
where
rmm_no
is the number of the RMM shelf where the card was replaced
ckt_no
is the number of the first circuit where the NT2X57 card is physically
located.
Example of a MAP response:
LAST CIRCUIT = 14
POST CKT IDLED
SHORT CLLI IS:
OK, CLLI POSTED
POST
13
TTP 6–006
CKT TYPE
OG TESTEQ RMM 0 0
5
Send any faulty cards for repair according to local procedure.
6
Record the following items in office records:
date the card was replaced
serial number of the card
symptoms that prompted replacement of the card
Go to step 8.
7
Obtain further assistance in replacing this card by contacting the personnel
responsible for higher level of support.
8
You have completed this procedure.
OPM card replacement procedures
1147
DELQ
BUSY Q
PM NO.
COM LANG
OAUSD 0
DMS-100 Family OPM Maintenance Manual XPM14 and up
NT2X57
in an OPM RMM
DIG
STA S R DOT TE R
IDL
8-53
(end)