Clearing PM PES critical, major, minor alarms
At the MAP terminal
1
Enter this procedure from a PM system level alarm clearing procedure step.
This step must identify a PM alarm associated with an OPM fault.
If an alarm continues to be audible, silence the alarm. To silence the alarm,
type
>MAPCI;MTC;sSIL
and press the Enter key.
2
To enter the PES MAP level, type
>PM;PES
and press the Enter key.
3
Examine the display to determine the most important alarm condition. Refer
to the alarm condition description at step 6.
4
To post the most important alarm condition, type
>POST condition
and press the Enter key.
where
condition
is the condition (red or amber)
A display like the following one appears on the MAP display.
OPM alarm clearing procedures
critical, major, minor
ATTENTION
DMS-100 Family OPM Maintenance Manual XPM14 and up
7-115
PM PES
(continued)