Table 1 Circuit breaker assignment for FSP in OPM
CB10
CB11
The FSP NT6X25BC in the NT8X01AB, AC, BB and BC contains the
following:
OPM grounding network
The cabinet ground bar in the end-access compartment connects to the OPM
principal GND. The user provides the GND according to local utility codes
and operating company requirements. Maximum recommended
ground-to-earth resistance is 25 Ω.
Refer to the following figures:
Optional
Optional
nine dc circuit breakers to control power distribution to each electronic unit
and two additional circuit breakers. These circuit breakers are CB10 and
CB11. The CB10 and CB11 can connect to optional equipment like the
fiber units and channel banks. Refer to the previous table for breaker
assignments.
eight QFF-type fuses to fuse dc links to alarms, fans and SD circuit packs
OPM Main Ground Bar Terminations NT8X01AA OPM-640/NT8X01BA
OPM-256
OPM Grounding Network NT8X01AB OPM-640/NT8X01BB OPM-256
OPM Grounding Network NT8X01AC OPM-640/NT8X01BC OPM-256
DMS-100 Family OPM Maintenance Manual ISN07 (TDM)/SN07 (DMS) and up
OPM maintenance summary 1-19
Optional equipment shelf (only in the NT8X01AB,
AC, BB and BC)
Optional equipment shelf (only in the NT8X01AB,
AC, BB and BC)