8-192 OPM card replacement procedures
NT6X74
in an OPM RMM
At the MAP display
3
LAST CIRCUIT = 27
POST CKT IDLED
SHORT CLLI IS:
OK, CLLI POSTED
POST
TTP 6–006
CKT TYPE
OG
4
5
6
297-8361-550 Standard 04.01 September 2000
(continued)
Access the TTP level of the MAP and post the RMM that contains the card to
be replaced by typing
>MAPCI;MTC;TRKS;TTP;POST P RMM rmm_no
and pressing the Enter key.
where
rmm_no
is the number of the RMM shelf in which the card is to be replaced
Example of a MAP response:
OTDA00
20
DELQ
PM NO.
MF RMM 0 0
OTWAON23DA00 2001
Check the status of the RMM.
If RMM status is
MB, PMB, RMB
other
Busy the trunks that are associated with the card to be replaced by typing
>BSY ALL
and pressing the Enter key.
Go to the PM level of the MAP and post the RMM by typing
>PM;POST RMM rmm_no
and pressing the Enter key.
where
rmm_no
is the number of the RMM shelf in which the card is to be replaced
Example of a MAP response:
BUSY Q
DIG
COM LANG
STA S R DOT TE R
LO
P_IDL
Do
step 8
step 5