7-52 OPM alarm clearing procedures
Ext FSP
OPM cabinet major
Alarm display
CM
.
Indication
The alarm code FSP appears under the EXT header of the alarm banner, at the
MTC level of the MAP display. The alarm code indicates an external frame
supervisory panel (FSP) major alarm. The number preceding the alarm code
indicates the number of frames or cabinets affected by the alarm. The letter M
below the alarm code indicates that the alarm class is major.
Meaning
This alarm means that one or more frames or cabinets in the office has a power
defect or a cooling unit defect.
Result
The impact on subscriber service depends on two conditions:
Common procedures
There are no common procedures.
Action
This procedure contains a summary flowchart and a list of steps. Use the
flowchart to review the procedure. Follow the steps to perform the procedure.
297-8361-550 Standard 04.01 September 2000
MS
IOD
Net
.
.
the characteristics of the fault
the type of frame or cabinet that has the fault
PM
CCS
.
.
.
Lns
Trks
Ext
.
.
1FSP
M
Appl
.