7-110 OPM alarm clearing procedures
PM PES
critical, major, minor
297-8361-550 Standard 04.01 September 2000
(continued)
condition of rectifiers
FL0
condition of rectifier 0
.
no rectifier fault detected
F
rectifier failed to detect its output
FL1 condition of rectifier 1
.
no rectifier fault detected
F
rectifier failed to detect its output
CL0 current limiting condition of rectifier 0
.
current limiting circuitry not active
F
current limiting circuitry active
CL1 current limiting condition of rectifier 1
.
current limiting circuitry not active
F
current limiting circuitry active
temp
internal temperature of the OPM
EHT
extremely high temp. in OPM
.
extremely high temp. not detected
F
extremely high temp. detected
ELT
extremely low temp. in OPM
.
extremely low temp. not detected
F
extremely low temp. detected
HBT
Extremely high battery temp. in OPM
.
not detected
F
Extremely high battery temp.
detected
door
position of doors on the OPM
FRNT
position of the front door
.
door closed
o
door open
SIDE
position of the side door
.
door closed
o
door open
ECU
condition of environmental control unit (ECU)
.
ECU not faulty
F
ECU faulty
Extremely high battery temp.