Nortel DMS-100 Series Maintenance Manual page 262

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

7-42 OPM alarm clearing procedures
LCM
major
(continued)
At the OPM site
6
7
8
At the MAP terminal
9
10
11
297-8361-550 Standard 04.01 September 2000
If fault indicated
is ManB
Inspect the ringing generator to see if the LED is lit.
If the LED
is lit
is not lit
To power up the ringing generator move the circuit breaker to the ON position.
(The LED goes OFF.) These switches are:
RG 0 corresponds to LCM unit 0 CB2
RG 1 corresponds to LCM unit 1 CB3
Determine if power restores to the ringing generator.
If power
restores
does not restore
To identify C-side links to the host PM, type
>TRNSL C
and press the Enter key.
Example of a MAP response:
Link 0: LTC 0
Link 1: LTC 0
To post the host peripheral (LGC, LTC, or RCC), type
>POST
pm_type pm_no
and press the Enter key.
where
pm_type
is LGC, LTC, or RCC
pm_no
is the number of the host peripheral
To identify the P-side links that have faults, type
>TRNSL P
Do
step 17
Do
step 7
step 16
Do
step 23
step 16
2; Cap MS; Status: OK
6; Cap MS; Status: SysB
;MsgCond: OPN
;MsgCond: CLS