Control And Status Word 1 - Siemens SINAMICS G120D Operating Instructions Manual

Distributed converter, control units with encoder evaluation
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

6.2.4.1

Control and status word 1

Control word 1 (STW1)
Bit
0
1
2
3
4
5
6
7
8, 9 Reserved
10
11
12
Converter with control units CU240D-2
Operating Instructions, 07/2016, FW V4.7 SP6, A5E34262100B AD
Significance
Telegram 20
All other tele-
grams
0 = OFF1
0 → 1 = ON
0 = OFF2
1 = No OFF2
0 = Quick stop (OFF3)
1 = No quick stop (OFF3)
0 = Inhibit operation
1 = Enable operation
0 = Disable RFG
1 = Do not disable RFG
0 = Stop RFG
1 = Enable RFG
0 = Inhibit setpoint
1 = Enable setpoint
0 → 1 = Acknowledge faults
0 = No control via PLC
1 = Control via PLC
1 = Direction reversal
Not used
Explanation
The motor brakes with the ramp-down time
p1121 of the ramp-function generator. The
inverter switches off the motor at standstill.
The inverter goes into the "ready" state. If, in
addition bit 3 = 1, then the inverter switches on
the motor.
Switch off the motor immediately, the motor
then coasts down to a standstill.
The motor can be switched on (ON com-
mand).
Quick stop: The motor brakes with the OFF3
ramp-down time p1135 down to standstill.
The motor can be switched on (ON com-
mand).
Immediately switch-off motor (cancel pulses).
Switch-on motor (pulses can be enabled).
The inverter immediately sets its ramp-
function generator output to 0.
The ramp-function generator can be enabled.
The output of the ramp-function generator
stops at the actual value.
The output of the ramp-function generator
follows the setpoint.
The inverter brakes the motor with the ramp-
down time p1121 of the ramp-function genera-
tor.
Motor accelerates with the ramp-up time
p1120 to the setpoint.
Acknowledge fault. If the ON command is still
active, the inverter switches to"closing lockout"
state.
Inverter ignores the process data from the
fieldbus.
Control via fieldbus, inverter accepts the pro-
cess data from the fieldbus.
Invert setpoint in the inverter.
Advanced commissioning
6.2 Inverter control
Signal inter-
connection
in the in-
verter
p0840[0] =
r2090.0
p0844[0] =
r2090.1
p0848[0] =
r2090.2
p0852[0] =
r2090.3
p1140[0] =
r2090.4
p1141[0] =
r2090.5
p1142[0] =
r2090.6
p2103[0] =
r2090.7
p0854[0] =
r2090.10
p1113[0] =
r2090.11
123