Co/Bo: Status Word Monitoring 1 / Zsw Monitor 1 - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Value:
0:
1:
2:
3:
4:
5:
Dependency:
See also: p2182, p2183, p2184, p2185, p2186, p2187, p2188, p2189, p2190, p2192, r2198, p3230, p3231, p3232
See also: A07891, A07892, A07893, F07894, F07895, F07896, F07898, A07920, A07921, A07922, F07923, F07924,
F07925, F07936
Note
p2193 = 4, 5 can only be combined with p2181 = 7, 8.
r2197.0...13

CO/BO: Status word monitoring 1 / ZSW monitor 1

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Display and BICO output for the first status word of the monitoring functions.
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
10
11
13
NOTICE
For bit 06:
When the overspeed is reached, this bit is set and F07901 output immediately following this. The bit is canceled again
as soon as the next pulse inhibit is present.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Monitoring switched out
Monitoring torque and load drop
Monitoring speed and load drop
Monitoring load drop
Monitoring pump and load failure
Monitoring fan and load failure
Signal name
|n_act| <= n_min p1080
|n_act| <= speed threshold value 2 p2155
|n_act| > speed threshold value 2 p2155
n_act >= 0
|n_act| >= n_set
|n_act| <= n_standstill p1226
|n_act| > n_max
Speed setpoint - actual value deviation in tolerance t_off
I_act >= I_threshold value p2170
Vdc_act <= Vdc_threshold value p2172
Vdc_act > Vdc_threshold value p2172
Output load is not present
|n_act| > n_max (F07901)
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Parameters
7.2 Parameter list
Data type: Unsigned16
Dynamic index: -
Function diagram: 2534
Factory setting:
-
0 signal
FP
No
8022
No
8010
No
8010
No
8011
No
8022
No
8022
No
8010
No
8011
No
8022
No
8022
No
8022
No
8022
No
-
789

Advertisement

Table of Contents
loading

Table of Contents