Commissioning
8.4 Commissioning using the AOP30 operator panel
p50100[D]
p50101[D]
p50102[D]
p50103[D]
p50114[D]
p2003
Note
For 2Q devices, the rated DC voltage of the SINAMICS DCM specified in the technical data,
can only be achieved if the α
order to reach the rated motor voltage (p50101[D]), the α
When you have finished entering the motor data, choose "Continue" underneath the final
parameter value and activate with <F5> (OK).

Encoder selection

p50083[D]
Analog tachometer screen
p50741[D]
p2000
Pulse encoder screen
p0400[E]
p0404[E]
p0405[E]
p0408[E]
p2000
284
Rated armature current
Rated armature voltage
Rated excitation current
Minimum excitation current (optional)
Thermal time constant for motor
See the section titled "Thermal overload protection for the DC motor
(I
t monitoring of the motor)"
2
Enter the rated torque
• If specified: refer to the manufacturer's specifications of the motor
• Or calculate from rating plate specifications for power and rated speed:
p2003 = 9550 x rated power [in kW] / rated speed [in rpm]
limit (p50150[D]) is set to 5°. The factory setting is 30°. In
G
Actual speed controller value selection
Tachometer voltage at maximum speed
Reference speed
Encoder type selection
Encoder configuration active
Square-wave encoder A/B
Rotary encoder pulse no.
Reference speed
limit must also be changed to 5°.
G
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A