Analog Inputs; Advanced Commissioning - Siemens SINAMICS G110M Operating Instructions Manual

Distributed converter for simogear geared motors
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

Advanced commissioning

6.2 Inverter control
r0052.1
r0052.2
r0052.3
r0052.4
r0052.5
r0052.6
r0052.7
r0052.8
A complete list of the binector outputs is provided in the List Manual.
Changing the function of a digital output - example
Advanced settings
You can invert the signal of the digital output using parameter p0748.
For more information, see the parameter list and the function block diagram 2241 of the List
Manual.
6.2.2.3

Analog inputs

Changing the function of the analog input
134
Drive ready for operation
Drive running
Drive fault active
OFF2 active
OFF3 active
Closing lockout active
Drive alarm active
Setpoint/actual value discrepancy
r0052.11
Alarm: Motor current/torque limit
r0052.12
Brake active
r0052.13
Motor overload
r0052.14
Motor CW rotation
r0052.15
Inverter overload
r0053.0
DC braking active
r0053.2
f_actual > p1080 (f_min)
r0053.6
f_actual ≥ setpoint (f_setpoint)
In order to output the fault message over the digital
output DO 1, you have to connect the DO 1 with the
fault message: Set p0731 = 52.3.
1. Define the analog input type using
parameter p0756 and the DIP
switches on the Control Unit for
current or voltage input.
2. Specify the function of the analog
input by interconnecting parameter
p0755 with a connector input CI of
your choice, for example as a speed
setpoint.
Distributed converter for SIMOGEAR geared motors