Parameters
7.2 Parameter list
Note
When changing p0776, the parameters of the scaling characteristic (p0777, p0778, p0779, p0780) are overwritten with
the following default values:
For p0776 = 0, p0777 is set to 0.0 %, p0778 = 0.0 mA, p0779 = 100.0 % and p0780 to 20.0 mA.
For p0776 = 1, p0777 is set to 0.0 %, p0778 = 0.0 V, p0779 = 100.0 % and p0780 to 10.0 V.
For p0776 = 2, p0777 is set to 0.0 %, p0778 = 4.0 mA, p0779 = 100.0 % and p0780 to 20.0 mA.
X202: IO module terminal
p0777[0...2]

CU analog outputs characteristic value x1 / CU AO char x1

Access level: 2
Can be changed: T, U
Unit group: -
Min:
-1000.00 [%]
Description:
Sets the scaling characteristic for the analog outputs.
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 1st value pair of the characteristic.
Index:
[0] = AO0 (X133 12/13)
[1] = AO1 (X202 85/86)
[2] = AO2 (X202 83/84)
Dependency:
See also: p0776
NOTICE
This parameter is automatically overwritten when changing p0776 (type of analog outputs).
Note
The parameters for the characteristic do not have a limiting effect.
X202: IO module terminal
p0778[0...2]

CU analog outputs characteristic value y1 / CU AO char y1

Access level: 2
Can be changed: T, U
Unit group: -
Min:
-20.000 [V]
Description:
Sets the scaling characteristic for the analog outputs.
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 1st value pair of the
characteristic.
Index:
[0] = AO0 (X133 12/13)
[1] = AO1 (X202 85/86)
[2] = AO2 (X202 83/84)
Dependency:
The unit of this parameter (V or mA) depends on the analog output type.
See also: p0776
NOTICE
This parameter is automatically overwritten when changing p0776 (type of analog outputs).
Note
The parameters for the characteristic do not have a limiting effect.
X202: IO module terminal
574
Calculated: -
Scaling: -
Unit selection: -
Max:
1000.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
20.000 [V]
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 9572
Factory setting:
0.00 [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 9572
Factory setting:
0.000 [V]
SINAMICS G120X converter