6.2

Ambient conditions

Property
Ambient conditions for transport in the transport packaging
Climatic ambient conditions
Mechanical ambient condi-
tions
Protection against chemical
substances
Biological environmental
conditions
Ambient conditions for long-term storage in the product packaging
Climatic ambient conditions
Protection against chemical
substances
Biological environmental
conditions
Ambient conditions in operation
Installation altitude
Climatic ambient conditions
1)
Mechanical ambient condi-
tions
Protection against chemical
substances
Biological environmental
conditions
Pollution
Cooling
Cooling air
Increased ruggedness regarding temperature range and relative humidity; therefore better than 3K3 according to IEC
1)
60721-3-3: 2002
Observe the permissible ambient temperatures for the Control Unit and possibly the operator panel (IOP-2 or BOP-2).
2)
Power Module PM240P-2
Hardware Installation Manual, 06/2020, A5E37800827C AD
Version
- 40 °C ... + 70 °C, according to Class 2K4 to EN 60721-3-2:1997
maximum humidity 95% at 40 °C
Shocks and vibrations permissible according to 2M3 to IEC 60721-3-2:1997
Protected according to Class 2C2 to IEC 60721-3-2:1997
Suitable according to Class 2B1 to IEC 60721-3-2:1997
- 25 °C ... + 55 °C, according to Class 1K3 to IEC 60721-3-1:1997
Protected according to Class 1C2 to IEC 60721-3-1:1997
Suitable according to Class 1B1 to IEC 60721-3-1:1997
Up to 1000 m above sea level without derating,
> 1000 m
Restrictions for special ambient conditions (Page 69)
Frame sizes FSD ... FSF temperature range
in operation acc. to LO: -20 °C ... +40 °C
in operation acc. to HO: -20 °C ... +50 °C
for higher temperatures
Restrictions for special ambient conditions (Page 69)
Relative humidity: 5 ... 95%, condensation not permitted
Oil mist, ice formation, condensation, dripping water, spraying water, splashing water
and water jets are not permitted
Vibration levels permissible according to Class 3M1 to EN 60721-3-3:2002
Shocks permissible according to Class 3M1 to EN 60721-3-3:2002
Protected according to 3C2 to IEC 60721-3-3:2002
Suitable according to 3B1 to IEC 60721-3-3: 2002
Suitable for environments with degree of pollution 2 according to EN 61800-5-1
Forced air cooling AF, according to EN 60146
Clean and dry air
6.2 Ambient conditions