Power Unit Hardware Properties / Pu Hw Property; Power Unit Application / Pu Application - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Parameters
7.2 Parameter list
Note
For parallel circuit configurations, the parameter index is assigned to a power unit.
r0204[0...n]

Power unit hardware properties / PU HW property

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Displays the properties supported by the power unit hardware.
Bit field:
Bit
01
07
08
12
14
15
p0205

Power unit application / PU application

Access level: 1
Can be changed: C2(1, 2)
Unit group: -
Min:
0
Description:
The duty cycles can be overloaded provided that the drive converter is operated with its base load current before and
after the overload. This is based on a load duty cycle of 300 s.
Value:
0:
1:
6:
7:
Dependency:
See also: r3996
NOTICE
The parameter value is not reset when the factory setting is restored (see p0010 = 30, p0970).
When the power unit use is changed, short-term communication interruptions may occur.
Note
When the parameter is changed, all of the motor parameters (p0305 ... p0311), the technological application (p0500)
and the control mode (p1300) are pre-assigned according to the selected application. The parameter has no influence
when calculating the thermal overload.
p0205 can only be changed to the settings that are saved in the power unit EEPROM.
p0205
Power unit application / PU application
G120X_DP (PM330),
Access level: 1
G120X_PN (PM330),
Can be changed: C2(1, 2)
G120X_USS (PM330)
Unit group: -
Min:
0
Description:
The duty cycles can be overloaded provided that the drive converter is operated with its base load current before and
after the overload. This is based on a load duty cycle of 300 s.
Value:
0:
502
Signal name
RFI filter available
F3E regenerative feedback into the line supply
Internal Braking Module
Safe Brake Control (SBC) supported
Internal LC output filter
Line voltage
Load duty cycle with high overload for vector drives
Load duty cycle with low overload for vector drives
S1 duty cycle (for internal use)
S6 duty cycle (for internal use)
Load duty cycle with high overload for vector drives
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
No
Yes
1-phase
Calculated: -
Scaling: -
Unit selection: -
Max:
7
Calculated: -
Scaling: -
Unit selection: -
Max:
1
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: Unsigned32
Dynamic index: PDS, p0120
Function diagram: -
Factory setting:
-
0 signal
FP
No
-
No
-
No
-
Yes
-
No
-
3-phase
-
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
0
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
1