Commissioning via the built-in BOP
5.6 Function commissioning
5.6.3.15

Running the converter in cavitation protection mode

Functionality
Cavitation occurs when air bubbles are generated around the surface of the impeller,
resulting in pump damage, unexpected noise, and decreased flow or pressure of the pipe
system. The cavitation protection will generate a fault/warning when cavitation conditions are
deemed to be present. If the converter gets no feedback from the pump transducer, it will trip
to prevent cavitation damage. This function saves the maintenance efforts and extends the
lifetime expectancy.
Setting parameters
Parameter
Function
P2360[0...2] Enable cavitation protection
P2361[0...2] Cavitation threshold [%]
P2362[0...2]
Cavitation protection time [s]
130
Setting
This parameter enables the cavitation protection function.
= 1: Fault
= 2: Warn
This parameter defines the feedback threshold over which a fault/warning is
triggered, as a percentage (%).
Range: 0.00 to 200.00 (factory default: 40.00)
This parameter sets the time for which cavitation conditions have to be pre-
sent before a fault/warning is triggered.
Range: 0 to 65000 (factory default: 30)
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012