Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F31152 (N, A)
Encoder 1: Maximum input frequency exceeded
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, ENC, VECTOR_G
Component:
Sensor Module Encoder 1
Reaction:
Vector: ENCODER (IASC/DCBRK, NONE, OFF1, OFF2, OFF3, STOP2)
Infeed: ENCODER (NONE, OFF1, OFF2)
Acknowledge:
PULSE INHIBIT
Cause:
The maximum input frequency of the encoder evaluation has been exceeded.
Fault value (r0949, interpret decimal):
Actual input frequency in Hz.
See also: p0408 (Rotary encoder pulse number)
Remedy:
- reduce the speed.
- Use an encoder with a lower pulse number (p0408).
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F31153 (N, A)
Encoder 1: Identification error
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, ENC, VECTOR_G
Component:
Sensor Module Encoder 1
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
An error has occurred when identifying the encoder (waiting) p0400 = 10100.
The connected encoder was not able to be identified.
Fault value (r0949, interpret hexadecimal):
Bit 0: Data length incorrect.
See also: p0400 (Encoder type selection)
Remedy:
Manually configure the encoder according to the data sheet.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F31160 (N, A)
Encoder 1: Analog sensor channel A failed
Message value:
%1
Message class:
Actual position/speed value incorrect or not available (11)
Drive object:
B_INF, ENC, VECTOR_G
Component:
Encoder 1
Reaction:
Vector: ENCODER (IASC/DCBRK, NONE)
Infeed: ENCODER (NONE)
Acknowledge:
PULSE INHIBIT
Cause:
The input voltage of the analog sensor is outside the permissible limits.
Fault value (r0949, interpret decimal):
1: Input voltage outside detectable measuring range.
2: Input voltage outside the measuring range set in (p4673).
3: The absolute value of the input voltage has exceeded the range limit (p4676).
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
LOCAL
Propagation:
LOCAL
Propagation:
LOCAL
4 Faults and alarms
4.2 List of faults and alarms
1731