Remedy:
Replace battery.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F32150 (N, A)
Encoder 2: Initialization error
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
Sensor Module Encoder 2
Reaction:
OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2)
Acknowledge:
PULSE INHIBIT
Cause:
Encoder functionality selected in p0404 is not operating correctly.
Fault value (r0949, interpret hexadecimal):
Encoder malfunction.
The bit assignment corresponds to that of p0404 (e.g. bit 5 set: Error track C/D).
Remedy:
- check that p0404 is correctly set.
- check the encoder type used (incremental/absolute) and for SMCxx, the encoder cable.
- if relevant, note additional fault messages that describe the fault in detail.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F32151 (N, A)
Encoder 2: Encoder speed for initialization AB too high
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
Sensor Module Encoder 2
Reaction:
OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2)
Acknowledge:
PULSE INHIBIT
Cause:
The encoder speed is too high while initializing the Sensor Module.
Remedy:
Reduce the speed of the encoder accordingly during initialization.
If necessary, deactivate monitoring (p0437.29).
See also: p0437 (Sensor Module configuration extended)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F32152 (N, A)
Encoder 2: Maximum input frequency exceeded
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
Sensor Module Encoder 2
Reaction:
OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2)
Acknowledge:
PULSE INHIBIT
Cause:
The maximum input frequency of the encoder evaluation has been exceeded.
Fault value (r0949, interpret decimal):
Actual input frequency in Hz.
See also: p0408 (Rotary encoder pulse number)
Remedy:
- reduce the speed.
- Use an encoder with a lower pulse number (p0408).
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
LOCAL
Propagation:
LOCAL
Propagation:
LOCAL
4 Faults and alarms
4.2 List of faults and alarms
1777