11/2006
300950
Axis %1 drive %2 is not safely referenced
Parameters:
%1 = Axis number
%2 = Drive number
Definitions:
No stop reaction is initiated. The message will be present during enabling of the functions SN/SE until
the axis status "Axis safely referenced" has been reached.
Request: In monitoring cycle.
1) The axis is not referenced or
2) The user enable for this axis is missing or was canceled. This can occur, for example, if the axis
was moved after the machine was switched off and the standstill position which was stored is therefore
no longer correct.
This message prompts the user to confirm the actual position. To do this, you must determine the
position, e.g. as follows:
- Measure the position.
- Move to a known position.
Reaction:
Alarm display.
Remedy:
Please inform the authorized personnel/service department. If no safe automatic referencing is
possible, the user must confirm the new position via the softkey. This user confirmation marks this
position as safe, that means the axis status "Axis safely referenced" is reached.
Warning:
If the axis has not been safely referenced and the user has not confirmed, the following applies:
- The safe cams are still active and not yet safe.
- The safe limit positions are not yet active.
Program
Alarm display showing cause of alarm disappears. No further operator action necessary.
Continuation:
300951
Axis %1 drive %2 test stop is running
Parameters:
%1 = Axis number
%2 = Drive number
Definitions:
The pulses are deleted.
1. If the positive acknowledgement is not received within the time configured in MD 1357:
$MD_SAFE_PULSE_DIS_CHECK_TIME (time for checking the pulse deletion), STOP A is triggered.
2. If pulse deletion is acknowledged within the configured time in the drive, no stop reaction is
triggered. This message will be displayed during selection via the SGE "Test stop selection" until the
selection is canceled.The test stop has been activated by the user by setting the SGE "Test stop
selection". If the user cancels the SGE "Test stop selection", the message will also be cancelled.
Request: In monitoring cycle.
The test stop has been activated by the user by setting the SGE "Test stop selection". The pulses are
deleted.
1. If the positive acknowledgement is not received within the time configured in MD 1357:
$MD_SAFE_PULSE_DIS_CHECK_TIME (time for checking the pulse deletion), STOP A is triggered.
2. If pulse deletion is acknowledged within the configured time in the drive, no stop reaction is
triggered. This message will be displayed during selection via the SGE "Test stop selection" until the
selection is canceled.
Reaction:
Alarm display.
Remedy:
The message disappears automatically if the test is terminated by the user by clearing the SGE "Test
stop selection". If STOP A is triggered, restart is only possible with POWER ON.
Program
Alarm display showing cause of alarm disappears. No further operator action necessary.
Continuation:
300952
Axis %1 drive %2 acceptance test is active
Parameters:
%1 = Axis number
%2 = Drive number
Definitions:
The acceptance test has been activated by the user.
Reaction:
Alarm display.
Remedy:
This message disappears automatically when the test is finished.
Program
Alarm display showing cause of alarm disappears. No further operator action necessary.
Continuation:
© Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), 11/2006 Edition
Overview of Alarms
SIMODRIVE alarms
2-771