11/2006
14055
Channel %1 block %2 impermissible NC language substitution, error
code %3
Parameters:
%1 = Channel number
%2 = Block number, label
%3 = Error code
Definitions:
This alarm occurs in conjunction with an NC language substitution configured in
$MA_AXIS_LANG_SUB_MASK. Error code %3 gives more detailed information about the cause of
the problem:
Error code:
1: Several events had been programmed, causing the replacement cycle to be called. Only one
substitution is allowed per part program line.
2: A non-modal synchronized action had also been programmed for the part program line with the NC
language substitution.
3: The system variables $P_SUB_SPOSIT and $P_SUB_SPOSMODE were called outside a
replacement cycle.
Reaction:
Correction block is reorganized.
Interpreter stop
Interface signals are set.
Alarm display.
Remedy:
Modify the NC program
Program
Clear alarm with NC START or RESET key and continue the program.
Continuation:
14060
Channel %1 block %2 invalid skip level with differential block skip
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
With "Differential block skip", a skip level greater than 7 has been specified. (In packet 1 specification
of a value for the skip level is rejected by the converter as a syntax error, i.e. the only possibility is a
"Suppress block" ON/OFF on one level).
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Enter a skip level (number behind the slash) less than 8.
Program
Clear alarm with NC START or RESET key and continue the program.
Continuation:
14070
Channel %1 block %2 memory for variables not sufficient for subroutine
call
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
A called subroutine cannot be processed (opened), either because the internal data memory to be
created for general purposes is not large enough, or because the available memory for the local
program variables is too small. The alarm can only occur in MDI mode.
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Analyze the part program section:
1. Has the most useful data type always been selected in the variable definitions? (For example REAL
for data bits is poor; BOOL would be better)
2. Can local variables be replaced by global variables?
Program
Clear alarm with the RESET key. Restart part program
Continuation:
© Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), 11/2006 Edition
Overview of Alarms
NCK alarms
2-203