10.5 Technical data dependent on the power

10.5
Technical data dependent on the power
Feature
Data
FSAA ... FSC
Required line impe‐
1 % ≤ U
dance U
For U
K
inverter with the next higher power rating.
Power factor λ
0.7 without line reactor for U
0.85 with line reactor for U
Pulse frequency
Factory setting: 4 kHz
Change in 2‑kHz steps:
2 kHz ... 16 kHz
If you increase the pulse frequency above the factory setting then the inverter reduces the maximum
output current.
Permissible ambi‐
The permissible ambient temperature depends on the following conditions:
ent temperature
● Frame size (FS) of the inverter
● Inverter fieldbus interface
● Operator panel
Device-dependent technical data
The inverter input currents specified in the following are applicable for an input voltage of 400 V.
406
< 4 %
K
< 1 %, we recommend a line reactor or an
K
≥ 1 %
K
< 1 %
K
Restrictions for special ambient conditions (Page 414)
FSD ... FSF
U
< 4 %
K
A line reactor is not required.
> 0.9
Factory setting:
4 kHz for inverters with an LO base load power
< 75 kW
2 kHz for inverters with an LO base load power
≥ 75 kW
Change in 2‑kHz steps:
2 kHz ... 16 kHz for inverters with an LO base load
power < 55 kW
2 kHz ... 8 kHz for inverters with an LO base load
power = 55 kW ... 90 kW
2 kHz ... 4 kHz for inverters with an LO base load
power ≥ 110 kW
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF