p29530[0...5]

Multi-pump control absolute operating hours / Mpc op_hrs

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.00 [h]
Description:
Displays the total operating hours for motors.
The display can only be reset to zero.
Index:
[0] = Motor 1 operating hours
[1] = Motor 2 operating hours
[2] = Motor 3 operating hours
[3] = Motor 4 operating hours
[4] = Motor 5 operating hours
[5] = Motor 6 operating hours
Note
Absolute operating hours means the total operating hours since the motor's initial operation.
p29531

Multi-pump control maximum time for continuous operation / Mpc t_max

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.01 [h]
Description:
Time limit for the continuous operation of motors.
Continuous operation is measured starting from when a motor is ON and It ends when a motor is OFF.
p29533

Multi-pump control switch-off sequence / Mpc sw_off seq

Access level: 3
Can be changed: T
Unit group: -
Min:
0
Description:
Selection of the response used to stop the motors when the OFF command is sent.
For p29533 = 1:
when OFF1:
In this mode the motors connecting with the mains stop one at a time separated by one ramp down delay in the reverse
order in which they were switched on. The converter controlled motor stops with a normal ramp down (OFF1) which
commences when the first motor connecting with the mains is switched off.
The time set in p29537 is applied as a delay time between the disconnection of each line motor.
Then speed-regulated motor is ramp down following OFF1 behavior.
In the case of OFF2 and OFF3, the motors connecting to the line are switched off immediately with the OFF
command(same behavior as with p29533=0).Then the converter controlled motor is ramp down following OFF2 or
OFF3 behavior.
Value:
0:
1:
918
Switch-in/switch-out active
All motors active
Switch Over not possible
Alarm active
Halt normal
Halt sequential
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max:
340.28235E36 [h]
Calculated: -
Scaling: -
Unit selection: -
Max:
100000.00 [h]
Calculated: -
Scaling: -
Unit selection: -
Max:
1
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
No
-
No
-
No
-
No
-
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
0.00 [h]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
24.00 [h]
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
0
SINAMICS G120X converter