Co: Technology Controller Fixed Value 15 / Tec_Ctr Fix Val 15; Bi: Technology Controller Fixed Value Selection Bit 0; Bi: Technology Controller Fixed Value Selection Bit 1; Bi: Technology Controller Fixed Value Selection Bit 2 - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

p2215[0...n]

CO: Technology controller fixed value 15 / Tec_ctr fix val 15

Access level: 2
Can be changed: T, U
Unit group: 9_1
Min:
-200.00 [%]
Description:
Sets the value for fixed value 15 of the technology controller.
Dependency:
See also: p2220, p2221, p2222, p2223, r2224, r2229
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2216[0...n]
Technology controller fixed value selection method / Tec_ctr FixVal sel
Access level: 2
Can be changed: T
Unit group: -
Min:
1
Description:
Sets the method to select the fixed setpoints.
Value:
1:
2:
p2220[0...n]
BI: Technology controller fixed value selection bit 0 / Tec_ctrl sel bit 0
Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source to select a fixed value of the technology controller.
Dependency:
See also: p2221, p2222, p2223
p2221[0...n]
BI: Technology controller fixed value selection bit 1 / Tec_ctrl sel bit 1
Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source to select a fixed value of the technology controller.
Dependency:
See also: p2220, p2222, p2223
p2222[0...n]
BI: Technology controller fixed value selection bit 2 / Tec_ctrl sel bit 2
Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source to select a fixed value of the technology controller.
Dependency:
See also: p2220, p2221, p2223
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Direct selection
Binary selection
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max:
200.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
2
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Parameters
7.2 Parameter list
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 7950
Factory setting:
150.00 [%]
Data type: Integer16
Dynamic index: DDS, p0180
Function diagram: 7950, 7951
Factory setting:
1
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 7950, 7951
Factory setting:
0
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 7950, 7951
Factory setting:
0
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 7950, 7951
Factory setting:
0
795