Table 7- 22
Parameter Description
p1055
p1056
p1058
p1059
7.4.5

Specifying the motor speed via the fieldbus

If you enter the setpoint via a fieldbus, you must connect the inverter to a higher-level
control. For additional information, see chapter Configuring the fieldbus (Page 101).
Interconnecting the fieldbus with the setpoint source
You have two options for using the fieldbus as the setpoint source:
1. Using p0015, select a configuration that is suitable for your application.
2. Interconnect main setpoint p1070 with the fieldbus.
Table 7- 23
Parameter
r2050[x]
r2090[x]
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
Parameters for the "Jog" function
Signal source for jogging 1 - jog bit 0 (factory setting: 0)
If you wish to jog via a digital input, then set p1055 = 722.x
Signal source for jogging 2 - jog bit 1 (factory setting: 0)
If you wish to jog via a digital input, then set p1056 = 722.x
Jogging 1 speed setpoint (factory setting, 150 rpm)
Jogging 2 speed setpoint (factory setting, 150 rpm)
Please refer to the section titled Select interface assignments (Page 46) to find out which
configurations are available for your inverter.
Fieldbus as setpoint source
Setpoint source
Receive word no. x from RS485 interface
Receive word no. x from PROFIBUS interface
Functions
7.4 Setpoint sources
165