7.2 Parameter list
05
07
08
09
Note
The motor data identification must be executed when using the voltage measurement.
p0251[0...n]

Operating hours counter power unit fan / PU fan t_oper

G120X_DP (PM330),
Access level: 3
G120X_PN (PM330),
Can be changed: T
G120X_USS (PM330)
Unit group: -
Min:
0 [h]
Description:
Displays the power unit fan operating hours.
The number of hours operated can only be reset to 0 in this parameter (e.g. after a fan has been replaced).
Dependency:
See also: p0252
See also: A30042
Note
For liquid-cooled chassis power units, the operating hours of the inner fan are displayed in p0251 and not in p0254.
p0252

Maximum operating time power unit fan / PU fan t_oper max

G120X_DP (PM330),
Access level: 4
G120X_PN (PM330),
Can be changed: T
G120X_USS (PM330)
Unit group: -
Min:
0 [h]
Description:
Sets the maximum operating time of the power unit fan.
The prealarm (warning) is output 500 hours before this set value.
The monitoring is deactivated with p0252 = 0.
Dependency:
See also: p0251
See also: A30042
Note
For PM330 power units, the maximum operating time of the fan on the power unit is saved and displayed in p0252. The
"Restore factory setting" function or a project download does not influence p0252. Users can manually change the
maximum operating time of the fan. The modified value is also saved to the power unit.
p0254[0...n]
Operating hours counter power unit fan inside the converter / PU inner fan t_op
G120X_DP (PM330),
Access level: 3
G120X_PN (PM330),
Can be changed: T
G120X_USS (PM330)
Unit group: -
Min:
0 [h]
Description:
Displays the power unit fan operating hours of the internal fan in the power unit.
The number of hours operated can only be reset to 0 in this parameter (e.g. after a fan has been replaced).
Dependency:
See also: A30042
Note
For liquid-cooled chassis power units, the operating hours of the inner fan are displayed in p0251 and not in p0254.
508
Use voltage measured values for flying restart
Voltage calibration when switching on
Voltage monitoring when switching on
Voltage monitoring cyclic
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max:
4294967295 [h]
Calculated: -
Scaling: -
Unit selection: -
Max:
100000 [h]
Calculated: -
Scaling: -
Unit selection: -
Max:
4294967295 [h]
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
No
-
No
-
No
-
No
-
Data type: Unsigned32
Dynamic index: PDS, p0120
Function diagram: -
Factory setting:
0 [h]
Data type: Unsigned32
Dynamic index: -
Function diagram: -
Factory setting:
40000 [h]
Data type: Unsigned32
Dynamic index: PDS, p0120