The converter exits hibernation mode 2 under the following conditions:
• The higher-level control goes into stop.
• The bus connection to the higher-level control is interrupted.
Parameters
The following list contains the parameters of the "Energy-saving mode" function.
Number
r5600
p5611.0...2
r5613.0...1
14.4.10.3

Setting the energy-saving mode

Overview
Various setting modes are available for the energy-saving mode.
Settings
Adjust the energy-saving mode using the information in the following table:
Table 14-14
Energy-saving mode settings
Settings
Inhibiting PROFIenergy
Transition to energy-saving
mode
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
Name
PROFIenergy energy-saving mode ID
PROFIenergy energy-saving properties general
PROFIenergy energy saving active/inactive
Parameters
Result
p5611.0 = 1
They block the reaction of the converter to PROFIenergy control com‐
mands.
In this case, the converter rejects the "Start_Pause" command with 50
hex (no appropriate pause mode).
p5611.2 = 0
With p5611.2 = 0, you enable the transition to energy-saving mode
from operating state S1 (switching on inhibited) or S2 (ready to switch
on).
 
With p5611.2 = 1
With p5611.2 = 1, you enable the transition to energy-saving mode
from operating states S3 (ready for operation) and S4 (operation).
Additional settings:
p5611.1 = 1
With the transition to energy-saving mode, the converter triggers an
OFF1 command and enters the switching on inhibited state (S1).
p5611.1 = 0
You use p5614 to interconnect a signal source that you use to switch
off the converter and place it in switching on inhibited state (S1).
Functions
14.4 PROFINET communication
Unit
 
 
 
379