4 Faults and alarms
4.2 List of faults and alarms
A50011 (F)
Ethernet/IP: configuration error
Message class:
Communication error to the higher-level control system (9)
Reaction:
NONE
Acknowledge:
NONE
Cause:
An EtherNet/IP controller attempts to establish a connection using an incorrect configuring telegram.
The telegram length set in the controller does not match the parameterization in the drive device.
Remedy:
Check the set telegram length.
For p0922 not equal to 999, then the length of the selected telegram applies.
For p0922 = 999, the maximum interconnected PZD (r2067) applies.
See also: p0922 (PROFIdrive PZD telegram selection), r2067 (PZD maximum interconnected)
A50020 (F)
PROFINET: Second controller missing
Message class:
Communication error to the higher-level control system (9)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The PROFINET function "Shared Device" has been activated (p8929 = 2). However, only the connection to a
PROFINET controller is present.
Remedy:
Check the configuration of the PROFINET controllers as well as the p8929 setting.
F50510
FBLOCKS: Logon of the run-time group rejected
Message class:
General drive fault (19)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
When the run-time groups of the free function blocks attempted to log on with the sampling time management, the
logon of at least one run-time group was rejected.
Too many different hardware sampling times may have been assigned to the free function blocks.
Remedy:
- check number of available hardware sampling times (T_sample < 8 ms) (r7903).
F50511
FBLOCKS: Memory no longer available for free function blocks
Message class:
General drive fault (19)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
When the free function blocks were activated, more memory was requested than was available on the Control Unit.
Remedy:
Not necessary.
A50513 (F)
FBLOCKS: Run sequence value already assigned
Message class:
General drive fault (19)
Reaction:
NONE
Acknowledge:
NONE
Cause:
An attempt was made to assign a run sequence value already assigned to a function block on this drive object to
another additional function block on the same drive object. A run sequence value can only be precisely assigned to
one function block on one drive object.
Remedy:
Set another value that is still available on this drive object for the run sequence.
A50517
FBLOCKS: Int. meas. active
Message class:
General drive fault (19)
Reaction:
NONE
Acknowledge:
NONE
Cause:
A Siemens internal measurement has been activated.
Remedy:
Carry out a POWER ON (switch-off/switch-on) for the Control Unit involved.
952
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313