4 Faults and alarms
4.2 List of faults and alarms
F07807
Drive: Short-circuit/ground fault detected
Message class:
Ground fault / inter-phase short-circuit detected (7)
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
A phase-phase short-circuit or ground fault was detected at the motor-side output terminals of the converter.
Fault value (r0949, interpret decimal):
1: Short-circuit, phase UV.
2: Short-circuit, phase UW.
3: Short-circuit, phase VW.
4: Ground fault with overcurrent.
1yxxx: Ground fault with current in phase U detected (y = pulse number, xxxx = component of the current in phase V
in per mille).
2yxxx: Ground fault with current in phase V detected (y = pulse number, xxxx = component of the current in phase U
in per mille).
Note:
Also when interchanging the line and motor cables is identified as a motor-side short circuit.
The ground fault test only functions when the motor is stationary.
Connecting to a motor that is either not de-energized or partially de-energized is possibly detected as ground fault.
Remedy:
- check the motor-side converter connection for a phase-phase short-circuit.
- rule-out interchanged line and motor cables.
- check for a ground fault.
For a ground fault the following applies:
- do not enable the pulses when connecting to a rotating motor without the "Flying restart" function activated (p1200).
- increase the de-energization time (p0347).
- increase pulse suppression delay time (p1228) to ensure standstill.
- if required, de-activate the monitoring (p1901).
F07810
Drive: Power unit EEPROM without rated data
Message class:
Hardware/software error (1)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
No rated data are stored in the power unit EEPROM.
See also: p0205 (Power unit application), r0206 (Rated power unit power), r0207 (Rated power unit current), r0208
(Rated power unit line supply voltage), r0209 (Power unit maximum current)
Remedy:
Replace the power unit or inform Siemens Customer Service.
A07850 (F)
External alarm 1
Message class:
External measured value / signal state outside the permissible range (16)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The condition for "External alarm 1" is satisfied.
Note:
The "External alarm 1" is initiated by a 1/0 edge via binector input p2112.
See also: p2112 (External alarm 1)
Remedy:
Eliminate the causes of this alarm.
A07851 (F)
External alarm 2
Message class:
External measured value / signal state outside the permissible range (16)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The condition for "External alarm 2" is satisfied.
Note:
The "External alarm 2" is initiated by a 1/0 edge via binector input p2116.
See also: p2116 (External alarm 2)
Remedy:
Eliminate the causes of this alarm.
890
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313