2 Parameters
2.2 List of parameters
6:
9999: Do not calculate
p20307
NOT 5 run sequence / NOT 5 RunSeq
CU240D-2_DP
Access level: 3
CU240D-2_PN
Can be changed: T
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
0
Description:
Setting parameter for the run sequence of instance NOT 5 within the run-time group set in p20306.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
p20308[0...3]
CI: ADD 2 inputs / ADD 2 inputs
CU240D-2_DP
Access level: 3
CU240D-2_PN
Can be changed: T
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
-
Description:
Sets the signal source of input quantities X0, X1, X2, X3 of instance ADD 2 of the adder.
Index:
[0] = Input X0
[1] = Input X1
[2] = Input X2
[3] = Input X3
r20309
CO: ADD 2 output Y / ADD 2 output Y
CU240D-2_DP
Access level: 3
CU240D-2_PN
Can be changed: -
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
-
Description:
Display parameter for the output quantity Y = X0 + X1 + X2 + X3 of instance ADD 2 of the adder.
p20310
ADD 2 run-time group / ADD 2 RTG
CU240D-2_DP
Access level: 3
CU240D-2_PN
Can be changed: T
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
5
Description:
Setting parameter for the run-time group in which the instance ADD 2 of the adder is to be called.
Value:
5:
6:
9999: Do not calculate
p20311
ADD 2 run sequence / ADD 2 RunSeq
CU240D-2_DP
Access level: 3
CU240D-2_PN
Can be changed: T
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
0
Description:
Setting parameter for the run sequence of instance ADD 2 within the run-time group set in p20310.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
546
Run-time group 6
Run-time group 5
Run-time group 6
Calculated: -
Scaling: -
Unit selection: -
Max
32000
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
9999
Calculated: -
Scaling: -
Unit selection: -
Max
32000
Data type: Unsigned16
Dyn. index: -
Func. diagram: 7216
Factory setting
780
Data type: U32 / FloatingPoint32
Dyn. index: -
Func. diagram: 7220
Factory setting
0
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7220
Factory setting
-
Data type: Integer16
Dyn. index: -
Func. diagram: 7220
Factory setting
9999
Data type: Unsigned16
Dyn. index: -
Func. diagram: 7220
Factory setting
800